Commander SE AC Drive

(This drive Series is no Longer available, Call Microcon for a replacement.)

 Specifications
  Environment
Ambient Operating
Temperature
-10ºC to 40ºC @ 6kHz.
-10ºC to 50ºC @ 3kHz
For SE Size 4 (@ 18.5kW) and all SE Size 5's.
-10ºC to 40ºC @ 3kHz
Cooling method Convection and forced convection, model dependent
Humidity 95% maximum non-condensing at 40ºC
Storage Temperature -40ºC to 60ºC
Altitude Derate the continuous output current by 1% for every 100m above 1000m to a maximum of 4000m.
Vibration Tested in accordance with IEC 68-2-34 and IEC 68-2-36
Mechanical Shock Tested in accordance with IEC 68-2-29
Enclosure NEMA 1 (IP 21)
Electromagnetic Immunity In compliance with EN61800-3 and EN50082-2
Electromagnetic Emissions In compliance with EN61800-3 second environment, without RFI filter.
EN50081-1*, EN500821-2 and EN50081-3 first environment with optional RFI filter. *Size 1 only
 
  AC Supply Requirements
Voltage 200V model: 200 to 240 VAC ±10%
400V model: 380 to 480 VAC ±10%
Phase 1ph and 3ph (Model dependent)
Maximum Supply Imbalance 2% negative phase sequence (3% voltage imbalance between phases)
Frequency 48 to 62 Hz
Input Displacement Power Factor 0.97
 
  Control
Switching Frequency 3, 6 and 12 kHz (Default value model dependent)
Output Frequency Up to 1000 Hz
Frequency Accuracy ±0.01% of full scale
Frequency Resolution 0.1Hz
Analog Input Resolution 10 Bit + sign (Qty 2)
Serial Communications ANSI 2-wire EIA485 via RJ45 connector. Baud rate is 4800, 9600 or 19,200
Braking DC injection braking standard.
Dynamic braking transistor standard (not available on Size 1)
 
  Protection
DC Bus Under-voltage Trip 200V model: 180 VDC
(approx 127 VAC line voltage)
400V model: 400 VDC
(approx 282 VAC line voltage)
DC Bus Overvoltage Trip 200V model: 420 VDC
(approx 299 VAC line voltage)
400V model: 830 VDC
(approx 587 VAC line voltage)
MOV Voltage Transient Protection 160 Joules, 1400 VDC clamping (Line to line and line to earth)
Drive Overload Trip Current overload value is exceeded.
Programmable to allow up to 150% of drive current for one minute
Instantaneous Over-current Trip 215% of drive rated current
Phase Loss Trip DC bus ripple threshold exceeded
Over-temperature Trip Drive heatsink temperature exceeds 95°C (203ºF)
Short Circuit Trip Protects against output phase to phase fault
Earth Fault Trip Protects against output phase to earth fault
Motor Thermal Trip Electronically protects the motor from overheating due to loading conditions
 
  Approvals & Listings
UL, cUL UL File Listed 8D14
IEC Meets IEC Vibration, Mechanical Shock and Electromagnetic Immunity Standards
CE Designed for marking
NEMA NEMA 1 enclosure type
ISO 9002 Certified Manufacturing Facility
ISO 14001 Certified Manufacturing Facility

 